川消消防控制器的鏈接需要注意什么?
來源:http://www.xintli.net/ 日期:2022-05-01
對消防火災報警控制器進行自檢功能檢查。
Check the self inspection function of the fire alarm controller.
對可測量相關參數進行查看和記錄,如回路電流等。
Check and record relevant measurable parameters, such as loop current, etc.
公共場所煙感器、溫感器安裝檢查,與底座接觸是否良好,外觀是否潔凈完好。
Check the installation of smoke and temperature sensors in public places, whether they are in good contact with the base and whether the appearance is clean and intact.
每次隨機抽取不低于5%的煙感或溫感,噴煙或加熱后查視報警是否正確。
No less than 5% smoke or temperature sense shall be randomly selected each time. Check whether the alarm is correct after smoking or heating.
手動報警按鈕,檢查安裝是否牢固,有無破損及丟失。

Check whether the manual alarm button is firmly installed, damaged or lost.
每次隨機抽取不低于5%的手動報警按鈕,進行模擬報警,測試報警功能是否正常。
At least 5% of the manual alarm buttons are randomly selected each time to simulate the alarm and test whether the alarm function is normal.
對樓層內各模塊箱進行外觀檢查,外接線是否固定良好。
Check the appearance of each module box in the floor and whether the external wiring is well fixed.
對聯動控制柜上的按鈕每次按10%的比例進行功能試驗,控制功能正常。
The function test of the button on the linkage control cabinet is carried out according to the proportion of 10% each time, and the control function is normal.
對火災報警控制柜、聯動控制柜等進行清掃除塵。線路松動,應進行緊固。對自檢、消音、復位功能檢查,主電源與備用電源切換、報警檢查。
Clean and dust the fire alarm control cabinet and linkage control cabinet. If the line is loose, it shall be fastened. Check the self inspection, silencing and reset functions, and check the switching between main power supply and standby power supply and alarm.