    當前位置:首頁 > 新聞中心泡沫滅火系統的調試應符合什么規定?

    泡沫滅火系統的調試應符合什么規定?

    來源:http://www.xintli.net/ 日期:2023-05-22

    (1)當為手動滅火系統時,應以手動控制的方式進行一次噴水試驗;當為自動滅火系統時,應以手動和自動控制的方式各進行一次噴水試驗,系統流量、泡沫產生裝置的工作壓力、比例混合裝置的工作壓力、系統的響應時間均應達到設計要求。
    (1) When using a manual fire extinguishing system, a water spray test should be conducted in a manually controlled manner; In case of an automatic fire extinguishing system, a water spray test shall be carried out manually and automatically. The system flow, the working pressure of the foam generating device, the working pressure of the proportioning device, and the response time of the system shall all meet the design requirements.
    檢查數量:當為手動滅火系統時,選擇遠的防護區或儲罐;當為自動滅火系統時,選擇所需泡沫混合液流量大和遠的兩個防護區或儲罐分別以手動和自動的方式進行試驗。
    Inspection quantity: When using a manual fire extinguishing system, select a remote protective area or storage tank; In case of automatic fire extinguishing system, two protection areas or storage tanks with large and far foam mixture flow shall be selected for test in manual and automatic ways respectively.
    (2)川消小編提醒,低倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗;當為自動滅火系統時,應以自動控制的方式進行;噴射泡沫的時間不宜小于1min;實測泡沫混合液的流量、發泡倍數及到達遠防護區或儲罐的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (2) Sichuan Xiaobian reminds that the low expansion foam fire extinguishing system has completed the water spraying test according to the provisions of paragraph 1 of this article, and the foam spraying test is conducted after the water is emptied; When it is an automatic fire extinguishing system, it should be carried out in an automatic control manner; The time of spraying foam should not be less than 1min; The measured flow, foaming ratio and time to reach the far protection area or storage tank of foam mixture shall meet the design requirements, and the mixing ratio shall not be lower than that of the selected foam mixture.
    川消
    檢查數量:選擇遠的防護區或儲罐,進行一次試驗。
    Inspection quantity: Select a remote protective area or storage tank for one test.
    (3)中倍數、高倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗,當為自動滅火系統時,應以自動控制的方式對防護區進行噴泡沫試驗,噴射泡沫的時間不宜小于30S,實測泡沫供給速率及自接到火災模擬信號開始噴泡沫的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (3) The medium and high expansion foam fire extinguishing systems shall be sprayed with foam after the completion of water spraying test according to the provisions of paragraph 1 of this article. In case of automatic fire extinguishing systems, foam spraying test shall be carried out in the protection area in an automatic control manner. The time of foam spraying shall not be less than 30s. The measured foam supply rate and the time from receiving the fire simulation signal to starting to spray foam shall meet the design requirements, The mixing ratio shall not be lower than that of the selected foam concentrate.
    檢查數量:全數檢查。
    Inspection quantity: All inspections.
    泡沫滅火系統的調試應符合以上所講內容規定,希望對您有所幫助,更多事項就來我們網站http://www.xintli.net留言咨詢吧!
    The commissioning of the foam fire extinguishing system should comply with the above provisions. I hope it will be helpful to you. For more information, please come to our website http://www.xintli.net Leave a message for consultation!
    上一篇:自動跟蹤定位射流滅火系統應符合這樣的要求!
    下一篇:川消自動噴水滅火設備故障的5個常見原因

    相關產品 / Related products

    中文字幕无码精品亚洲资源网久久| 少妇伦子伦精品无码STYLES| 欧洲精品久久久av无码电影| 久久久久中文字幕| 高清无码在线视频| 亚洲gv猛男gv无码男同短文| 亚洲日韩VA无码中文字幕| 日韩亚洲不卡在线视频中文字幕在线观看| 亚洲成a人片在线观看无码专区| 最近最新高清免费中文字幕 | 中文字幕手机在线视频| 特级小箩利无码毛片| 东京热加勒比无码视频| 亚洲av中文无码乱人伦在线咪咕| 成人麻豆日韩在无码视频 | 精品亚洲成A人无码成A在线观看| 亚洲一区无码中文字幕| 无码精品人妻一区二区三区影院| 国产精品无码av在线播放| 无码国产福利av私拍| 无码午夜成人1000部免费视频| 无码国产精品一区二区免费 | 熟妇人妻无码中文字幕| 中文字幕日韩第十页在线观看| 亚洲欧美日韩国产中文| 中文字幕丰满伦子无码| 中文字幕乱码一区二区免费| 亚洲人成无码www久久久| 精品无码久久久久久国产| 日韩AV无码中文无码不卡电影| 少妇无码一区二区三区| 无码AV天堂一区二区三区| 日韩人妻无码精品久久免费一| 欧洲成人午夜精品无码区久久| 久久国产亚洲精品无码| 潮喷大喷水系列无码久久精品| av区无码字幕中文色| 少妇中文无码高清| 熟妇人妻不卡中文字幕| 一本大道香蕉中文在线高清| 久久久久久无码国产精品中文字幕 |