    泡沫滅火系統的調試應符合什么規定?

    來源:http://www.xintli.net/ 日期:2023-05-22

    (1)當為手動滅火系統時,應以手動控制的方式進行一次噴水試驗;當為自動滅火系統時,應以手動和自動控制的方式各進行一次噴水試驗,系統流量、泡沫產生裝置的工作壓力、比例混合裝置的工作壓力、系統的響應時間均應達到設計要求。
    (1) When using a manual fire extinguishing system, a water spray test should be conducted in a manually controlled manner; In case of an automatic fire extinguishing system, a water spray test shall be carried out manually and automatically. The system flow, the working pressure of the foam generating device, the working pressure of the proportioning device, and the response time of the system shall all meet the design requirements.
    檢查數量:當為手動滅火系統時,選擇遠的防護區或儲罐;當為自動滅火系統時,選擇所需泡沫混合液流量大和遠的兩個防護區或儲罐分別以手動和自動的方式進行試驗。
    Inspection quantity: When using a manual fire extinguishing system, select a remote protective area or storage tank; In case of automatic fire extinguishing system, two protection areas or storage tanks with large and far foam mixture flow shall be selected for test in manual and automatic ways respectively.
    (2)川消小編提醒,低倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗;當為自動滅火系統時,應以自動控制的方式進行;噴射泡沫的時間不宜小于1min;實測泡沫混合液的流量、發泡倍數及到達遠防護區或儲罐的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (2) Sichuan Xiaobian reminds that the low expansion foam fire extinguishing system has completed the water spraying test according to the provisions of paragraph 1 of this article, and the foam spraying test is conducted after the water is emptied; When it is an automatic fire extinguishing system, it should be carried out in an automatic control manner; The time of spraying foam should not be less than 1min; The measured flow, foaming ratio and time to reach the far protection area or storage tank of foam mixture shall meet the design requirements, and the mixing ratio shall not be lower than that of the selected foam mixture.
    川消
    檢查數量:選擇遠的防護區或儲罐,進行一次試驗。
    Inspection quantity: Select a remote protective area or storage tank for one test.
    (3)中倍數、高倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗,當為自動滅火系統時,應以自動控制的方式對防護區進行噴泡沫試驗,噴射泡沫的時間不宜小于30S,實測泡沫供給速率及自接到火災模擬信號開始噴泡沫的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (3) The medium and high expansion foam fire extinguishing systems shall be sprayed with foam after the completion of water spraying test according to the provisions of paragraph 1 of this article. In case of automatic fire extinguishing systems, foam spraying test shall be carried out in the protection area in an automatic control manner. The time of foam spraying shall not be less than 30s. The measured foam supply rate and the time from receiving the fire simulation signal to starting to spray foam shall meet the design requirements, The mixing ratio shall not be lower than that of the selected foam concentrate.
    檢查數量:全數檢查。
    Inspection quantity: All inspections.
    泡沫滅火系統的調試應符合以上所講內容規定,希望對您有所幫助,更多事項就來我們網站http://www.xintli.net留言咨詢吧!
    The commissioning of the foam fire extinguishing system should comply with the above provisions. I hope it will be helpful to you. For more information, please come to our website http://www.xintli.net Leave a message for consultation!
    上一篇:自動跟蹤定位射流滅火系統應符合這樣的要求!
    下一篇:川消自動噴水滅火設備故障的5個常見原因

    相關產品 / Related products

    精品人妻无码专区中文字幕| 国产乱码精品一区二区三区中文| 欧美 亚洲 日韩 中文2019| 亚洲日韩av无码| 18禁网站免费无遮挡无码中文| AV无码人妻中文字幕| 中文字幕有码无码AV| 熟妇人妻中文字幕无码老熟妇| 国产精品无码专区在线观看| 自拍偷在线精品自拍偷无码专区| 国产精品中文字幕在线观看| 91精品无码久久久久久五月天 | 人妻少妇精品无码专区二区| 最近的中文字幕大全免费8| 永久免费无码网站在线观看个| 久久久久亚洲精品无码蜜桃| 中文一国产一无码一日韩| 在线中文字幕播放| 中文字幕精品亚洲无线码一区| 久久久久久无码国产精品中文字幕| 亚洲国产精品无码久久一线| 免费看成人AA片无码视频吃奶| 久久中文字幕视频、最近更新 | 天堂在/线中文在线资源官网| 亚洲AV中文无码乱人伦在线视色| 久久精品无码专区免费青青| 永久免费av无码入口国语片| 日本无码WWW在线视频观看| 精品人妻无码专区中文字幕| 日本中文字幕一区二区有码在线| 在线欧美中文字幕农村电影| 中文字幕无码一区二区三区本日| 无码精品前田一区二区| 国产亚洲精品无码专区| 91精品久久久久久无码| 日韩免费a级毛片无码a∨| 国产日产欧洲无码视频无遮挡| 国产成人无码A区在线观看视频 | 久久精品中文无码资源站| 日日摸夜夜爽无码毛片精选| 久久精品无码一区二区WWW|